LT-FR  4-20 mA & RS485 Transmitter for AC Phase Angle and Power Factor DIN Rail Transmitter

MLT-FR | 4-20 mA & Serial Data Output | AC Phase Angle and Power Factor | DIN Rail Transmitter

Phase Angle Measurement

Phase angle measurement by digital phase meter

Phase angle in degrees indicates the phase lead or lag between two periodic signals of the same period, as determined from their zero crossings. These two signals will typically be the voltage and current applied to a load. As illustrated, the phase angle in degrees is +360*P1/P.

The Micron Meters Phase angle transmitter transmits the lead or lag in degrees from 0° to 360° between two periodic signals of the same period. In the illustration to the right, phase angle is 360*P1/P. The signals are applied to the Channel A and B inputs of the Micron dual-channel pulse input signal conditioner board. A resolution of 1°, 0.1° or 0.01° is selectable. Accuracy is 0.01% up to 100 Hz, 0.1% at 1 kHz, and 1% at 10 kHz.

Power Factor Measurement

The power factor of an AC power system is the ratio of real power in watts (W) divided by apparent power in volt-amperes (VA). For sinusoidal signals, power factor is the cosine of phase angle.

The Micron power factor transmitter computes power factor as the cosine of phase angle. Power factor readings can range from 1.000 to 0.000 with three decimal places and an accuracy of 0.1% for sinusoidal signals at 50/60 Hz power line frequency. While power factor is always positive, the meter artificially assigns a minus sign to power factor for negative phase angles, and it sets power factor to 0 for phase angles greater than 90°.

Designed for flexibility

Signal conditioner board used with Micron Phase Transmitter

Phase angle and power factor are determined by timing crystal clock pulses over a specified gate time which is selectable from 10 ms to 199.99 s. By selecting the minimum gate time of 10 ms, the update rate can be up to 20/s for 50/60 Hz AC line frequency. Improved accuracy is obtained by making the gate time long enough so that multiple cycles can be averaged.

Exceptional Accuracy and Stability. Micron transmitters determine frequency by taking the inverse of period as measured with a calibrated quartz crystal time base. This results in extremely accurate and stable 6-digit internal readings (±999,999 counts), which are then processed in software. The analog output is generated by an ultra-linear 16-bit (65,536 step) digital-to-analog converter (DAC) for 0.02% output accuracy. The update rate of the transmitter output is a programmed gate time + 30 ms + 0-2 signal periods. For a 60 Hz signal, the update rate would be 20 per second. Such fast update rates are ideal for alarm and control.

Standard features of Micron MLT transmitters include:

  • 4-20 mA, 0-10V or -10V to +10V analog transmitter output, isolated, jumper-selectable and user scalable. All selections provide 16-bit (0.0015%) resolution of output span and 0.02% output accuracy of a reading from -99,999 to +99,999 counts that is also transmitted digitally. Output isolation from signal and power grounds eliminates potential ground loop problems.
  • Serial communications output, RS232 or RS485 (half or full duplex), jumper selectable. Three protocols are user selectable: Modbus RTU, Modbus ASCII, or Custom ASCII. Modbus operation is fully compliant with Modbus Over Serial Line Specification V1.0 (2002). The Custom ASCII protocol is simpler than the Modbus protocol and is recommended when all devices are Micron units.
  • Dual solid state relays, isolated, for alarm or control. Rated 120 mA at 130 Vac or 170 Vdc.
  • Transducer excitation output, isolated. User selectable 5V@100 mA, 10V@120 mA or 24V@50 mA.
  • Universal 85-264 Vac power. Low-voltage 10-48 Vdc or 12-32 Vac power is optional.

Easy Transmitter programming is via the Instrument Setup Software, which runs on a PC under MS Windows. This software can be downloaded from this website at no charge. The required transmitter-to-PC interface cable is available. (P/N CBL04).

  MLT-FR  Phase Angle Measurement Transmitter | Support Library
  Data Sheet | User Manual

Select Transmitter Type
Select Main Board Option
Extended Main Board: (required for phase functions)
Select Power Option
Select Input Option
Select Accessories
RS232 cable, 7ft. Connects RS232 screw terminals of LT transmitter to DB9 port of PC.
USB-to-DB9 adapter cable. Includes FTDI chip for compatibility with all versions of Windows. Combination of CBL02 and CBL04 connects PC USB port to LT RS232 port.
  • MLT | 4-20 mA & RS232/RS485 output transmitter
  • 8 | Extended Main Board
  • 0 | Isolated 85-264 Vac or 90-300 Vdc
  • FR Dual-Channel Pulse Input
$369.55
$369.55
Loading...